AFLEX-3003 Flexible VA Harmonics Tester
AFLEX -3005 Flexible Power Quality Tester
![](/en/images/stories/afeaturee.gif) |
![](/en/images/stories/flexibleac/pa30033005.gif) |
Power Analysis (3005)
- W, KW, H.P.
- VA ,KVA, VAR, KVAR
- PF, Phase Angle( Φ )
- Energy (WH, KWH)
- Dual displays (W+PF, VA+KVAR)
- Balanced 3 Φ Power Quality and Sequence
|
Harmonics Analysis
- True RMS (V and A)
- 3000 A
- Non-interrupted Harmonic Analysis ( V and A ) to the 50th Order in % and Magnitude
- Analysis of % THD-F and C.F.
- Fast Peak Function (33μs and 39μs)
- Programmable PT (1 to 250 )ratios
- Auto - Power - Off : 30 Minutes
|
Flexible probe , different from normal clamp meter, can pass through obstacles at will and wind many conducting wires simultaneously, max. diameter 170mm
![](/en/images/stories/aspee.gif)
AC Watt (50 or 65 Hz, PF 0.5 to 1, CT=1) AFLEX-3005 only
|
Range
|
Resolution
|
Accuray of reading
|
100.0 - 999.9 W
|
0.1 W
|
2% of range
|
1.000 - 9.999 KW
|
0.001 KW
|
2% of range
|
10.00 - 99.99 KW
|
0.01 KW
|
2% of range
|
100.0 - 999.9 KW
|
0.1 KW
|
2% of range
|
1000 - 9999 KW
|
1 KW
|
2% of range
|
|
AC Voltage(50 or 65 Hz, ,Auto Range, True RMS)
|
Range
|
Resolution
|
Accuracy of reading
|
4.0 V - 600 V
|
0.1 V
|
±0.5% ± 5dgts
|
|
Harmonics of AC Current in % and Magnitude(1 to 50th order)
|
Range
|
Resolution
|
Accuracy in %
|
Accuracy of Magnitude
|
1-20th
|
0.1%
|
±2%
|
±2% of reading ±0.4A
|
21st-50th
|
0.1%
|
±4% of reading ±2.0%
|
±4% of reading ± 0.4V
|
|
AC Current(50 or 65 Hz ,Auto Range, True RMS)
|
Range
|
Resolution
|
Accuracy of reading
|
0 - 300.0 A
|
0.1 A
|
1% of range
|
300.0 - 999.9 A
|
0.1 A
|
1% of range
|
1000 - 3000 A
|
1 A
|
1% of range
|
|
Harmonics of AC Voltage in % and Magnitude(1 to 50th order)
|
Range
|
Resolution
|
Accuracy in %
|
Accuracy of Magnitude
|
1-20th
|
0.1%
|
±2%
|
±2% ±0.5V
|
21st-50th
|
0.1%
|
±4% of reading ±2.0%
|
±4% of reading ± 0.5V
|
|
Total Harmonics Distortion(%THD-F,1 to 50th order)
|
Range
|
Resolution
|
Accuracy of reading
|
0.0-20%
|
0.1%
|
±2%
|
20-100%
|
0.1%
|
±6% of reading ±1%
|
100-999.9%
|
0.1%
|
±10% of reading ±1%
|
|