AFLEX-6300 Graphic Power Quality Analyzer
|
|
- Display of Overlapped Voltage and Current Waveform
- Maximum Demand (MD in W, KW, MW) with Programmable Period
- Harmonics Analysis ( V and I ) to the 50th Order
- Display of 25 Harmonics in One Screen with Waveform
- Display of waveform with Peak Values (512 Samples / Period), Datalogging of 32, 64, 128 or 256 Points/Cycles
- Analysis of Total Harmonics Distortion ( % THD-F )
- Graphic Phasor Diagram
- Programmable PT (1 to 3000) Ratios
|
- Capture 128 Transient Events ( Time + Cycles + Faults ) with Programmable Threshold(%), Can Also be Reviewed in LCD
- 50000 Records with Programmable Interval ( 1 to 6000 seconds)
- Output of Waveform, Power Parameters and 50 Harmonics at Command.
- Large Dot Matrix LCD Display with Backlight
- Optical Isolated RS-232C Interface
- Smart Datalogging to save Battery Power for Long-term Monitoring
- Built - in Calendar Clock for Data Logging
|
AC Watt ( 45 ~ 65 Hz, PF 0.5 to 1, CT=1 ) |
Range
|
Resolution
|
Accuracy of Readings
|
100.0 - 999.9 W
|
0.1 W
|
2% ± 8 dgts
|
1.000 - 9.999 KW
|
0.001 KW
|
2% ± 8 dgts
|
10.00 - 99.99 KW
|
0.01 KW
|
2% ± 8 dgts
|
100.0 - 999.9 KW
|
0.1 KW
|
2% ± 8 dgts
|
1000 - 9999KW
|
1 KW
|
2% ± 8 dgts
|
|
AC Current (45~65 Hz , True RMS)
|
Range
|
Range
|
Resolution
|
Accuracy of Readings
|
30 - 300 A
|
0.00 - 300 A
|
0.1 A
|
1 % of range ± 8 dgts
|
300 - 999.9 A
|
100.0 - 999.9 A
|
0.1 A
|
1 % of range ± 8 dgts
|
1000 - 3000 A
|
1000 - 3000 A
|
1 A
|
1 % of range ± 8 dgts
|
|
Harmonics of ACA in % and Magnitude (1 to 50th order)
|
Range
|
Resolution
|
Accuracy in %
|
Resolution
|
Accuracy in Magnitude
|
10.0 - 300 A
|
0.1 %
|
±1.0%
|
0.1 A
|
±1.0% of range ± 0.8A
|
1000 - 3000 A
|
0.1 %
|
±1.0%
|
1 A
|
±1.0% of range ± 3 A
|
|
Range
|
Resolution
|
Accuracy of Readings
|
0.00 - 1.00
|
0.01
|
± 1.5 % ± 8 digits
|
|
Harmonics of AC Voltage in % and Magnitude (1 to 50th order)
|
Range
|
Resolution
|
Accuracy in %
|
Resolution
|
Accuracy in Magnitude
|
50 - 600 V
|
0.1 %
|
±0.5%
|
0.1V
|
±0.5 % ± 0.5V
|
|
Range
|
Resolution
|
Accuracy of Readings
|
-180 ° to 180 ° (0 ° to 360 ° )
|
0.1 °
|
± 1 % ± 2 digits
|
|
AC Voltage ( 45 ~ 65 Hz, True RMS)
|
Range
|
Resolution
|
Accuracy of Readings
|
3 V - 600 V
|
0.1 V
|
± 0.5 % ± 5 dgts
|
|
Total Harmonics Distortion (% THD-F , 1 to 50th order)
|
Range
|
Resolution
|
Accuracy of Readings
|
0.0 - 999.9 %
|
0.1 %
|
± 0.5 % ± 5 digits
|
|
Conductor Size |
150 mm (approx.) |
Battery Type |
1.5 V SUM-3 *2 |
Display |
128*64 Dot Matrix |
Power Consumption |
10 mA (approx.)
|
Auto - Power - Off |
15 minutes |
LCD update rate |
2 times/sec |
Dimension |
130mm(L)*80mm(W)*43mm(H), 5.1"(L)*3.1"(W)*1.7"(H) |
Accessories |
Test lead*1 pair, Users manual*1, Batteries 1.5V*2 |
No. of Sample / Period |
512 ( V & A ), 256 (W) |
Operating Temperature |
-10 ℃ to 50 ℃ |
Operating Humidity |
< 85% RH |
Storage Temperature |
-20 ℃ to 60 ℃ |
Storage Humidity |
< 75 % RH |
Weight |
450g |
|