TES-3660 Autoranging Insulation Tester
|
|
- Large LCD with analog bar graph and digital display.
- 250V, 500V, 1000V output voltage for insulation M Ω testing.
- 4000M Ω insulation testing with automatically switch to voltage measurement.
- Lo Ω function for testing connections.
- Autodischarge of capacitive voltage charges.
- Last reading HOLD display.
- AC/DC voltage measurement up to 1000V.
- Manual data memory and read function (9 sets).
- Meets EN61557 and IEC1010-1, CAT III 1000V.
- Size : 235(L)x116(W)x54(H)mm (9.3"Lx4.6"Wx2.1"H)
|
Range
|
Resolution
|
Accuracy
|
Short Ciruit Current
|
40.00 Ω
|
0.01 Ω
|
± 2%rdg ± 2dgts
|
>200mA
|
|
AC Voltage (40Hz to 500Hz)
|
Range
|
Resolution
|
Accuracy
|
Sensitivity
|
Overload Protection
|
999V
|
1V
|
|
2V
|
1000Vrms
|
|
Resistance (Continuity<40 Ω on the 9999 Ω range)
|
Range
|
Resolution
|
Accuracy
|
Overload Protection
|
9999 Ω
|
1 Ω
|
1% ± 2 dgts
|
1000V
|
|
Range
|
Resolution
|
Accuracy
|
Sensitivity
|
Overload Protection
|
999V
|
1V
|
1% +2
|
2V
|
1000Vrms
|
|
Range |
1000M Ω /250V w/ autorange 1000M/400M/40M/4M |
2000M Ω /500V w/ autorange 2000M/400M/40M/4M |
4000M Ω /1000V w/ autorange 4000M/400M/40M/4M |
|
Resolution |
1000M Ω /250V, 1K Ω to 10 M Ω |
2000M Ω /500V, 1K Ω to 10 M Ω |
4000M Ω /1000V, 1K Ω to 10M Ω |
|
Accuracy |
3%rdg+5Count (under 1G Ω ) |
5%rdg+5Count (under 4G Ω ) |
|
Nominal Current |
>1mA |
|